Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01138
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01138 DENIED 5/10/05 1. According to Lighting Plan, lights are on Panel A. These lights are on Panel B. Please clarify. 2. VA load for Ckt B-17 is in the wrong space on panel schedule. Also, complete VA load for Phase C of new AC. 3. According to Panel Schedule, VA load for new Washing Machine is (3) (6720) = 20,160 VA. Load calculations account for 5340. Clarify. 4. Provide service load calculations. |
| 05/12/2005 | EGRANT1 | WWM | REVIEW | Needs Review | |
| 05/12/2005 | EGRANT1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/12/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |