Permit Number: T05CM01138
Parcel: 11105026F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01138
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01138 DENIED 5/10/05

1. According to Lighting Plan, lights are on Panel A. These lights are on Panel B. Please clarify.
2. VA load for Ckt B-17 is in the wrong space on panel schedule. Also, complete VA load for Phase C of new AC.
3. According to Panel Schedule, VA load for new Washing Machine is (3) (6720) = 20,160 VA. Load calculations account for 5340. Clarify.
4. Provide service load calculations.
05/12/2005 EGRANT1 WWM REVIEW Needs Review
05/12/2005 EGRANT1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2005 BETH GRANT OUT TO CUSTOMER Completed