Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
04/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01138 DENIED 4/21/05
1. In series rating, specify line and load size overcurrent protective device ratings.
2. Please document source of utility AFC. According to TEP SR-510, AFC for a 1200A Service is 75,100A.
3. Demonstrate that Panel P is not overloaded.
4. Demonstrate that Service is not overloaded.
04/21/2005 ROBERT SHERRY WATER REVIEW Approved
04/21/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) IT APPEARS LINTEL DETAIL / JUSTIFITION IS MISSING.IS THE LOCATION OF NEW TUBE STEEL COLUMN AT SLIDING DOOR CORRECT ON THE S-1 SHT.
04/21/2005 PATRICIA GILBERT ENGINEERING REVIEW Needs Review
04/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/10/2005 KMEDINA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/10/2005 KMEDINA1 OUT TO CUSTOMER Completed