Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01138
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/21/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01138 DENIED 4/21/05 1. In series rating, specify line and load size overcurrent protective device ratings. 2. Please document source of utility AFC. According to TEP SR-510, AFC for a 1200A Service is 75,100A. 3. Demonstrate that Panel P is not overloaded. 4. Demonstrate that Service is not overloaded. |
| 04/21/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/21/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) IT APPEARS LINTEL DETAIL / JUSTIFITION IS MISSING.IS THE LOCATION OF NEW TUBE STEEL COLUMN AT SLIDING DOOR CORRECT ON THE S-1 SHT. |
| 04/21/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review | |
| 04/21/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/10/2005 | KMEDINA1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/10/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |