Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01067
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/10/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide riser diagrams for the water and the waste & vet systems. 2. Show how the water piping was sized. 3. Provide a water and waste fixture schedule. 4. Show the expansion tank for the water heater. |
| 03/10/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/10/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/10/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 03/10/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that adequate ventilation is provided to the projrct space. |
| 03/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01067 DENIED 3/10/05 1. Provide power requirements for WH intended for re-circuiting to A-23,25. 2. Provide total VA for re-circuited WH and for removed WH. If there is a load increase, provide load calculation for panel schedule. 3. Provide conductor size for re-circuited WH. 4. Indicate overcurrent protection for re-circuited WH per NEC 422.11. 5. Provide disconnect for re-circuited WH per NEC 422 Part III. |
| 03/11/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/11/2005 | DROBEY1 | FIRE | REVIEW | Needs Review |