Permit Number: T05CM01067
Parcel: 134180030

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01067
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
03/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide riser diagrams for the water and the waste & vet systems.
2. Show how the water piping was sized.
3. Provide a water and waste fixture schedule.
4. Show the expansion tank for the water heater.
03/10/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
03/10/2005 ROBERT SHERRY WATER REVIEW Approved
03/10/2005 HEATHER THRALL ZONING REVIEW Approved
03/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that adequate ventilation is provided to the projrct space.
03/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01067 DENIED 3/10/05

1. Provide power requirements for WH intended for re-circuiting to A-23,25.
2. Provide total VA for re-circuited WH and for removed WH. If there is a load increase, provide load calculation for panel schedule.
3. Provide conductor size for re-circuited WH.
4. Indicate overcurrent protection for re-circuited WH per NEC 422.11.
5. Provide disconnect for re-circuited WH per NEC 422 Part III.
03/11/2005 GERRY KOZIOL WWM REVIEW Approved
03/11/2005 DROBEY1 FIRE REVIEW Needs Review