Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01043
Parcel: 11904609A

Address:
438 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T05CM01043
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/7/05
ACTIVITY NUMBER: T05CM01041, T05cm01042, T05CM01043
PROJECT NAME: Residence to office & Apt. Building to Residence & Office
PROJECT ADDRESS: 438 W. Ajo Way
ARCHITECT / ENGINEER: Arquitecto
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide site plan Sht. 1 of 5 without existing City of Tucson approval stamps.
2) Provide documents of lot combination.
3) Buildings on lot need to be justified per the 2003 IBC.
4) Table 602 north wall building "B" group R & B shall be 1 hr. fire resistance rating.
5) Justify bldg. "B" and bldg."A" per section 704.11 Parapets. Parapets shall be provided on exterior walls of buildings.
6) It appears garage has been demolished off of bldg. # 1. Please justify / clarify.
7) It appears two manufactured homes have been removed from site. Please clarify / justify.
8) It appears from records orig. building 'B' was apartments. Please justify / clarify demolition involved.
9) It appears from records orig. building 'A' was a residence. Please justify / clarify demolition involved.
10) Clarify building 'A' restroom facility meets ANSI A117.1 2003 standards.
11) Provide wall section between Bldg. #3 and Bldg. #2 with code analysis submittal sht. Clarify seperated / nonseperated use. See section 708.1 & 708.4.
12) Justify / clarify per section 903.2.7 for building #3. If non-seperated use most restrictive applies.
13) Change of occupancy on both buildings provide seismic and wind load calculations per 2003 IBC.
14) Buildings #3 smoke alarm per 907.2.10.1.2.
15) Building # 1 & #2 clarify per section 1008.1.8 - 1008.1.8.5 Door operations.
16) Porch design / structural calculations per 2003 IBC.
04/07/2005 DAVID RIVERA ZONING REVIEW Denied 03/29/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

Building plans permits cannot be approved until the site plan has been approved and stamped.
04/07/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied Building plans may not be approved prior to site plan approval.
04/07/2005 ROBERT SHERRY WATER REVIEW Approved
04/07/2005 JIM EGAN FIRE REVIEW Approved
04/07/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide complete mechanical plans to show compliance with the 2000 International Mechanical Code
2. Provide calculations to show compliance with the 2000 International Energy Conservation Code.
04/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plans for the building and site to show compliance with the 1994 Uniform Plumbing Code as modified by the State of Arizona.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2005 JMORALE1 OUT TO CUSTOMER Completed
04/15/2005 JMORALE1 REJECT SHELF Completed