Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2005 MADARA ENGINEERING BUILDING-RESIDENTIAL REVIEW Denied CITY OF TUCSON
BUILDING SAFETY DEPARTMENT
PERMIT APPLICATION PLAN CHECK COMMENT LIST
210 N. Stone Ave.
Tucson, AZ 85701
Phone: (520) 791-4475 Fax: (520) 791-4475

Date: June 1, 2005

To: Luis Martinez
1901 N. Dragoon
Tucson, AZ 85745
Phone: (520) 331-0874
Project name: 1710 W. Riverview Bl. #1, 2
Permit #: TO5CM01015
Structure: 1 story SFR Duplex
Occupancy: R-3
Occupant load: 5
Construction Type: V-B
Area S.F.: 1576 sq.ft. Project number: 18-5003-02


The first submittal plans for the above referenced project are in the process of Architectural, Structural, Plumbing, Mechanical and Electrical plan review for compliance with the City of Tucson ordinances and applicable codes. Corrections required are noted below. All corrections must be made to the original drawings and new complete and revised sets resubmitted along with a written response to each of the items listed below to facilitate a shorter back-check time.

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical review. These disciplines were checked only to the extent allowed by the documents provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL COMMENTS
Provide attic vent calculations to reflect all areas where ceilings are installed. Ref. R806. Reflect the net free area of each vent type and show all vent locations. Clarify how cross ventilation of each joist space is accomplished.
Specify thickness/ type of gypsum board for ceilings compliant with IRC Table R702.3.5 footnote d. Coordinate gypsum board thickness between notes on Sheet A2 and A7.
Provide plan information reflecting compliance with IRC N1101, 1102 for energy efficiency/ Building envelope (document the % of exterior wall that is glazing) and N1103 Tables N1103 through 1104.1 for equipment.
Clarify all locations where roof can drain over its own edge and coordinate with detail call outs showing parapet walls. Provide roof drains/ overflow drains and/or scupper as appropriate.

STRUCTURAL COMMENTS – Structural portion has been reviewed and approved;
PLUMBING COMMENTS
Clarify elevation of next upstream manhole rim and provide and/ or delete backwater valve as applicable pursuant to UPC 710. If not required the BWV should not be installed. If BWV is installed provide cleanouts on each side of BWV so that auger will not have to pass through the BWV.

MECHANICAL COMMENTS
Suggest louvered door or 100 square inch grille to interior for dryer make up instead of outside opening. See IRC 2439.4.

ELECTRICAL COMMENTS
Show arc fault circuit interrupter location in panel schedule. Ref. IRC E3802.11.
Coordinate service entrance section shown on Sheet A-6 with Architectural plans that are only showing two electric meters as 3 breakers are shown at meter section.
Review size of overcurrent devices on panel schedule for furnace, hot water heater and dryer for correctness. Also provide #1 copper feeders.
Clarify grounding electrode system. See IRC E3508, E3509, 3503.1 water bond.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plan reviewer at (602) 493-1963.
MADARA Engineering for the CITY OF TUCSON
By:
Michael Hundley
Vice-President
06/07/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied See previous comments provided under activity # T04CM05068. See FUP # T05OT00516 resubmittal requirements - $150.00 Engineering Study Review Fee due.