Permit Number: T05CM01015
Parcel: 11517037A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM01015
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2005 ANDREW CONNOR NPPO REVIEW Passed
03/24/2005 GERRY KOZIOL WWM REVIEW Completed
04/06/2005 MADARA ENGINEERING BUILDING-RESIDENTIAL REVIEW Denied CITY OF TUCSON
BUILDING SAFETY DEPARTMENT
PERMIT APPLICATION PLAN CHECK COMMENT LIST
210 N. Stone Ave.
Tucson, AZ 85701
Phone: (520) 791-4475 Fax: (520) 791-4475

Date: April 5, 2005

To: Luis Martinez
1901 N. Dragoon
Tucson, AZ 85745
Phone: (520) 331-0874
Project name: 1710 W. Riverview Bl. #1, 2
Permit #: TO5CM01015
Structure: 1 story SFR Duplex
Occupancy: R-3
Occupant load: 5
Construction Type: V-B
Area S.F.: 1576 sq.ft. Project number: 18-5003-01


The first submittal plans for the above referenced project are in the process of Architectural, Structural, Plumbing, Mechanical and Electrical plan review for compliance with the City of Tucson ordinances and applicable codes. Corrections required are noted below. All corrections must be made to the original drawings and new complete and revised sets resubmitted along with a written response to each of the items listed below to facilitate a shorter back-check time.

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical review. These disciplines were checked only to the extent allowed by the documents provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

ARCHITECTURAL COMMENTS
Specify the minimum finish floor elevation required. Ref. IRC R403.1.7.3.
Indicate any ceiling finishes at eave overhangs.
Provide attic vent calculations to reflect all areas where ceilings are installed. Ref. R806. Reflect the net free area of each vent type and show all vent locations.
Specify thickness/ type of gypsum board for ceilings compliant with IRC Table R702.3.5 footnote d. Coordinate gypsum board thickness between notes on Sheet A2 and A7.
Provide plan information reflecting compliance with IRC N1101, 1102 for energy efficiency/ Building envelope and N1103 Tables N1103 through 1104.1 for equipment.
Clarify all locations where roof can drain over its own edge and coordinate with detail call outs showing parapet walls. Provide roof drains/ overflow drains and/or scupper as appropriate.

STRUCTURAL COMMENTS
Update call outs on Roof and Floor framing plans to reflect correct drawing number and verify all details are pointed out correctly.

PLUMBING COMMENTS
Revise DWV diagram to reflect a duplex condition instead of a triplex.
Indicate size of waste line serving tub/shower in the DWV diagram.
Indicate plumbing fixture water flow rates.
Address expansion tank requirement for hot water heaters pursuant to the criteria outlined in UPC 608.3.
Provide cleanout for branch line to Kitchen sink. Ref. UPC 707.
Show pressure/temperature relief valve (s) at water heater with discharge to outside of the building or to an individual waste receptor located inside the building. Ref. UPC 608.
Hose bibbs and other openings with hose connection to be protected by vaccum breakers per UPC 603. Also include hose bibs in water pipe sizing calculation.
Clarify elevation of next upstream manhole rim and provide backwater valve if applicable pursuant to UPC 710.
Specify nonabsorbent surface at bathtub and shower walls and floor extending min. 6 ft. AFF. R307.2.

MECHANICAL COMMENTS
Specify back draft damper for dryer exhaust per IRC M1501.1.
Note to provide manufacturers installation instructions for dryer duct size to inspector at time of rough mechanical inspection for confirmation of compliance with IRC M1501.2 and with the length limitations of 1501.3.
Indicate range exhaust duct materials per IRC M1502.2 and back draft damper per M1502.1.
Provide 100 square inches make up air for dryer in closet.
Specify cfm of bathroom exhaust fans. Ref. IRC Table 1506.3.

ELECTRICAL COMMENTS
Provide receptacle within for wall space below smoke detector in Living room. Ref. IRC E3801.
Show arc fault circuit interrupter location in panel schedule. Ref. IRC E3802.11.
Provide lighting control from bedroom to exterior pursuant to IRC E3803.3.
Coordinate serving entrance section shown on Sheet A-6 with Architectural plans that are only showing two electric meters.
Review size of overcurrent devices on panel schedule for furnace, hot water heater and dryer for correctness.
Clarify grounding electrode system. See IRC E3508, E3509, 3503.1. UFER Ground in footings-20 ft. long, #4 bare copper wire, water and gas bonds.
Denote smoke detectors to be hard wired electric type with battery back up. Ref. IRC R313.2.
Provide WP/GFCI work receptacles within 25’ of outdoor HVAC units and show disconnect location for outdoor unit. Ref. IRC E3801.11.
Provide disconnect for hot water heaters. Ref. IRC Table E4001.5.
Denote range and dryer to be on 4 wire circuits. Ref. IRC E3808.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plan reviewer at (602) 493-1963.
MADARA Engineering for the CITY OF TUCSON
By:
Michael Hundley
Vice-President
04/18/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied See previous comments provided under activity # T04CM05068. See FUP # T05OT00516 resubmittal requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2005 DELMA ROBEY OUT TO CUSTOMER Completed