Review Details: COMMERCIAL TI
Permit Number - T05CM01006
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01006 DENIED 3/10/05 1. WH-1 draws 21.6A according to Sheet P1. Is protected by a 20A CB Sheet E1. Coordinate with Plumbing and clarify. It also appears that the WH needs a disconnect switch per NEC 422 Part III. This could be accomplished by specifying that the circuit breaker be capable of being locked in the open position. |
| 03/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 03/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/18/2005 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/18/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |