Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01006 DENIED 3/10/05

1. WH-1 draws 21.6A according to Sheet P1. Is protected by a 20A CB Sheet E1. Coordinate with Plumbing and clarify. It also appears that the WH needs a disconnect switch per NEC 422 Part III. This could be accomplished by specifying that the circuit breaker be capable of being locked in the open position.
03/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/18/2005 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2005 BETH GRANT OUT TO CUSTOMER Completed