Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01006
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The size and rating of the floor sink is based on the total rated discharge of the fixtures discharging to the floor sink. Revise the floor sink and the waste piping to comply with Sections 702.0 and 703.2, UPC 1994. 2. Provide information to show how the water pipes were sized. |
| 03/07/2005 | KELLY MARION | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/07/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/07/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the amount of outside air provided complies with Section 403.3.2, IMC 2000. 2. The minimum rewistance for the duct insulation is R-5. Reference Section 803.2.8, IECC 2000. |
| 03/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01006 DENIED 3/7/05 1. Fill in panel schedule for new and existing loads. Correct electrical load summary. 2. Provide calculations for service loading. Service has 9 tenants and it is not clear that addition of new loads will not overload service. 3. WH-1 draws 21.6A according to Sheet P1. Is protected by a 20A CB Sheet E1. Coordinate with Plumbing and clarify. |
| 03/07/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/11/2005 | EGRANT1 | WWM | REVIEW | Needs Review |