Review Details: COMMERCIAL TI

Permit Number - T05CM01006
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2005 JIM EGAN FIRE REVIEW Approved
03/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The size and rating of the floor sink is based on the total rated discharge of the fixtures discharging to the floor sink. Revise the floor sink and the waste piping to comply with Sections 702.0 and 703.2, UPC 1994.
2. Provide information to show how the water pipes were sized.
03/07/2005 KELLY MARION BUILDING-COMMERCIAL REVIEW Approved
03/07/2005 ROBERT SHERRY WATER REVIEW Approved
03/07/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
03/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the amount of outside air provided complies with Section 403.3.2, IMC 2000.
2. The minimum rewistance for the duct insulation is R-5. Reference Section 803.2.8, IECC 2000.
03/07/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01006 DENIED 3/7/05

1. Fill in panel schedule for new and existing loads. Correct electrical load summary.
2. Provide calculations for service loading. Service has 9 tenants and it is not clear that addition of new loads will not overload service.
3. WH-1 draws 21.6A according to Sheet P1. Is protected by a 20A CB Sheet E1. Coordinate with Plumbing and clarify.
03/07/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
03/11/2005 EGRANT1 WWM REVIEW Needs Review