Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00995
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00995 DENIED 3/7/05 1. Keynote 5 directs the Contractor to route homerun to panel indicated. Provide panel schedules and load calculations for all panels concerned. 2. Provide panel schedules and load calculations for all panels concerned on Keynote 2. 3. Provide more information on Owner Equipment on new Panel HF. Nature of the equipment, whether it is a motor load, power requirements. 4. Provide fault current rating for new panel. 5. Provide fault calculations sufficient to demonstrate proper AFC rating of new panel. 6. Provide load calculations for EDP. 7. Provide load calculations for service. |
| 03/07/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/07/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 03/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/08/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/11/2005 | KELLY MARION | BUILDING-COMMERCIAL | REVIEW | Approved | 1) PROVIDE VALUATION 2) CLARIFY / JUSTIFY PER 302.1.1 INCIDENTAL USE AREAS. WHY OVERHEAD DOORS FOR A 'B' OCCUPANCY USE. 3) PROVIDE LATERAL BRACING FOR NEW PARTITION WALL. 4) DOOR SWING IN THE DIRECTION OF EXIT PATH. 5) CLARIFY OCCUPANT LOAD FOR EACH SPACE. LABEL ROOMS. |
| 03/29/2005 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |