Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00995
Parcel: 14029037B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
03/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/07/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00995 DENIED 3/7/05

1. Keynote 5 directs the Contractor to route homerun to panel indicated. Provide panel schedules and load calculations for all panels concerned.
2. Provide panel schedules and load calculations for all panels concerned on Keynote 2.
3. Provide more information on Owner Equipment on new Panel HF. Nature of the equipment, whether it is a motor load, power requirements.
4. Provide fault current rating for new panel.
5. Provide fault calculations sufficient to demonstrate proper AFC rating of new panel.
6. Provide load calculations for EDP.
7. Provide load calculations for service.
03/07/2005 ROBERT SHERRY WATER REVIEW Approved
03/07/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
03/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/08/2005 JIM EGAN FIRE REVIEW Approved
03/11/2005 KELLY MARION BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE VALUATION
2) CLARIFY / JUSTIFY PER 302.1.1 INCIDENTAL USE AREAS. WHY OVERHEAD DOORS FOR A 'B' OCCUPANCY USE.
3) PROVIDE LATERAL BRACING FOR NEW PARTITION WALL.
4) DOOR SWING IN THE DIRECTION OF EXIT PATH.
5) CLARIFY OCCUPANT LOAD FOR EACH SPACE. LABEL ROOMS.
03/29/2005 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2005 BETH GRANT OUT TO CUSTOMER Completed