Permit Number: T05CM00990
Parcel: 11704058A

Address:
614 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00990
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2005 JIM EGAN FIRE REVIEW Approved
03/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the ventilation for the building complies with Section 401, IMC 2000.
03/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with Arizona State Amendments.
2. Provide material standards for all plumbing fixtures being provided by others. Reference Section 103.2.3, UPC 1994.
3. Recalculate the plumbing schedule using the fixture unit values shown on Tables 6-3 and 7-3, UPC 1994. Indicate the sizes of the existing drains and vents. Show the size of the building sewer. Reference Section 103.2.3, UPC 1994.
4. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, and valves. Reference Section 103.2.3, UPC 1994.
5. Provide the minimum plumbing facilities for the massage rooms as required by Section 7-137 of city of Tucson Ordinance number 9991.
6. Provide riser diagrams to show how the relocated plumbing fixtures are being connected to the existing waste and vent system. Reference Section 103.2.3, UPC 1994.
7. Provide cleanouts for all of the sinks. Reference Section 707.4, UPC 1994.
8. Show the location and size of the reduced pressure backflow preventer for the building water service.
03/10/2005 ROBERT SHERRY WATER REVIEW Approved
03/14/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Passed
03/30/2005 GERRY KOZIOL WWM REVIEW Denied NEEDS 8TH FLOOR REVIEW OF CONNECTION & CREDIT
04/04/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/4/05
ACTIVITY NUMBER: T05CM00990
PROJECT NAME: T.I. BEAUTY SALON
PROJECT ADDRESS: 320 W. Alturas
ARCHITECT / ENGINEER: Tom Spendiarian
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) It appears this location has not previously been permitted as combined suites, therefore you will need to meet the 2003 IBC code requirements.
2) Per section 2902.2 separate facilities are required for men and women based on occupant load. Each facility must meet ANSI A117.1-2003 or provide cost justification per 3409.6 exception 1.
3) Per section 1013 travel through a storage room to get to a restroom facility is not permitted. Also see section 1104 accessible route.
4) Indicate accessible entrance per section 1105.
5) Accessible parking space per section 1106 and table 1106.1.
6) Clarify openings between original two suites are in non-bearing walls. See wall that runs east and west from front of building water closet 2 room to laundry room in tbe back.
7) Proved wall section for in-fill framing.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2005 DELMA ROBEY OUT TO CUSTOMER Completed