Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00978
Parcel: 11006159B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00978
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. Provide two coordinated sets with revisions noted by Engineer of Record.
S2. Clarify if work to be done if more than two buildings originally processed (T05CM00977 and T05CM00978) to be worked on additional Permits required and work to be documented on drawings by EOR.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
08/02/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Load calculations for service for Units 1-6 are based on NEC 220.32. Basis for such computation is outlined in NEC 220.32 (C). On the calculation on the plans, this total, for one unit would be 22,598 VA, not 17,574. (17,574) (6) (0.44) = 135,588, not 105,444. (105444) (0.44) = 59,569, not 46,395. 46,395/240 = 249A, not 193 A. Typical comment for any such service.
2. Service appears overloaded. 4/0 ampacity is 230A, which is less than the 249A above. Typical comment for any such service.
3. Account for Unit 17 on the line diagram.
4. Note that the conductors emerging from the riser to the existing service wireway are service entrance conductors, not feeders.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2005 JMORALE1 OUT TO CUSTOMER Completed
08/05/2005 SUE REEVES REJECT SHELF Completed