Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00978
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | Provide hard-wired smoke detectors in each apartment unit, per IBC Section #907.2.10.1.2 and Section #34,in each room used for sleeping purposes, and in the common area leading to the sleeping rooms. Interconnection of the smoke detectors is required by IBC Section #907.2.10.3. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 06/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Meter Bank Calculation looks good up to the last two lines. Here the appliances for the 6 units are being added at 15,500 VA. Please justify this figure. Appliances to be accounted for are the 1200 VA refrigerator and the 5760 VA W/D. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 06/14/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |