Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00978
Parcel: 11006159B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00978
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved Provide hard-wired smoke detectors in each apartment unit, per IBC Section #907.2.10.1.2 and Section #34,in each room used for sleeping purposes, and in the common area leading to the sleeping rooms. Interconnection of the smoke detectors is required by IBC Section #907.2.10.3.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
06/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Meter Bank Calculation looks good up to the last two lines. Here the appliances for the 6 units are being added at 15,500 VA. Please justify this figure. Appliances to be accounted for are the 1200 VA refrigerator and the 5760 VA W/D.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2005 JMORALE1 OUT TO CUSTOMER Completed
06/14/2005 ANGIE SHOFFSTALL REJECT SHELF Completed