Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00978
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Meter Bank Calculation, which uses the demand factors in the optional calculation method per NEC 220.32, shall be revised. Per Section 220.32 (C), the Connected Load to which the demand factors of Table 220.32 shall be applied are itemized in (1)-(5) of this Section. Calculations on the plans use the 79A for each individual dwelling unit, which applied a demand factor of its own per NEC 220.30; this is the proper calculation for the feeder to an individual dwelling unit, but 220.30 does not apply to Multi-Family services. See the attached example. 2. Show size of service gutters and grounding electrode conductors. 3. Units 7 & 8 have a furnace according to Sheet E2. No such specification on the Mechanical schedules. Coordinate with Mechanical and clarify. 4. Provide a circuit for the fan coil (indoor) units to the Split System Heat Pumps. 5. Note that, in the load calculations for individual dwelling units, the divisor is 240, not 208. 6. On Sheet E1, the wording "BLDG 2861" needs to be changed to read "BLDG 2841." 7. Clarify scope of work on Sheet G1. According to this sheet, both BLDG 2861 AND BLDG 2841 are in the scope of work. |
| 05/10/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. Provide seal and signature of Structural Engineer on appropriate drawing/s. S2. Provide details of roof penetrations,including flashing materials and gage, roof jack, and roofing materials, etc. S3. Dimensionally locate units on roof plan. S4. Clarify and justify fire ratings including penetrations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/13/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 05/13/2005 | SUE REEVES | REJECT SHELF | Completed |