Permit Number - T05CM00977
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00977 DENIED 3/4/05 1. This is an incomplete review. The following comments need to be addressed before Electrical Review. 2. Indicate additional strip heating on Mechanical Schedule, or remove it from electrical load. Coordinate with Mechanical and clarify. 3. Provide power for the separate units on the Split System Heat Pump Shcedule, or remove this Schedule from Mechanical. 4. Provide size of electrical services. 5. Provide load calculations for services, not just the panel feeders. Provide size of electrical services. |
| 04/19/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 04/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |