Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00977
Parcel: 11006159B

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00977
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00977 DENIED 3/4/05
1. This is an incomplete review. The following comments need to be addressed before Electrical Review.
2. Indicate additional strip heating on Mechanical Schedule, or remove it from electrical load. Coordinate with Mechanical and clarify.
3. Provide power for the separate units on the Split System Heat Pump Shcedule, or remove this Schedule from Mechanical.
4. Provide size of electrical services.
5. Provide load calculations for services, not just the panel feeders. Provide size of electrical services.
04/19/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Passed
04/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review