Permit Number: T05CM00972
Parcel: 11504525C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T05CM00972
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2005 JIM EGAN FIRE REVIEW Approved
03/10/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
03/29/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/1/05
ACTIVITY NUMBER: T05CM00972
PROJECT NAME: Columbarium Addition First Christian Church
PROJECT ADDRESS: 740 E. Speedway
ARCHITECT / ENGINEER: Donald Smith
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Structural Engineer needs to Justify Seismic use group I. It appears to be part of structure with large occupant load and elementary school facilities / day care facilities.
2) Clarify header design & other modifications required at triangle portion of low roof to remain shall be designed & field directed by Structural Engineer during construction in consultation. For permitting purpose clarification is required and a revision can be processed later if necessary.
3) Where is section A3 cut? Please designate on floor plan.
4) Concrete pier design is per 16" sq. and sht. A1 allows 12" min. please justify.
5) Clarify & detail masonry tie for brick veneer to CMU block wall.
6) Clarify location for anchor bolts and Epoxy anchors per the structural calculation pg. 15.
7) Justify with calculations lintel sizing and reinforcing for lintel over door opening and wall section.
8) Permit will not be issued until special inspection form has been provided for Epoxy anchors.
04/05/2005 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/06/2005 DELMA ROBEY OUT TO CUSTOMER Completed