Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00938
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/24/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/12/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. Provide completed Code Review Checklist , this can be downloaded from our website, www.tucsonaz.gov/dsd, forms section. S2. Provide documents that conform to the 2003 International Building Code. S3. Show antenna attachment method on permit drawings, including material specifications, ref drawing C3. S4. Clarify occupancy group, U would 3 hour fire-rated separation from S1, perhaps this equipment room could be classified as S1 also, requiring no additional separation . S5. Special Inspection is required for the Antenna Mounting. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/29/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |