Permit Number: T05CM00933
Parcel: 124161400

Address:
835 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00933
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
04/11/2006 HEATHER THRALL ZONING REVIEW Denied TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: T05CM00933
835 E. 22nd Street, Maico Restaurant and Single Family Residence
Site Plan

TRANSMITTAL DATE: April 12, 2006

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please provide a note on both future and current site plans indicating truncated domes will be provided on all handicapped access ramps. Staff acknowledges a handicapped ramp detail on S 4a, however, this note should be on both plans with reference to S4a.

2. The future site plan shows a new sidewalk from Tyndall across the parking area to the buildings. This new sidewalk/ramps location cuts directly behind two public parking lot spaces, which is a safety concern and a conflict with DS 3-05. The sidewalk must be relocated around the perimeter of the parking spaces.

(Staff agreed to allow the handicapped ramp crossing behind the residential carport because it is a private parking space).

Please note, relocation of the sidewalk may affect the landscaping area, including the proposed 30" screen wall - and landscaping staff should be consulted prior to design.

3. Add the adjacent township, range and section numbers to the location map on both the current and future site plans.

4. Should you have any questions on this review, contact me at Heather.Thrall@tucsonaz.gov or at 791-4541x1156. I am willing to make an appointment to review the plan changes at the counter.


If you have any questions about this transmittal, please call (520) 791-5608.

HCT C:\planning\site\DSD\T0500933 835 e 22nd future plan.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised current and future site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
04/14/2006 SUE REEVES REJECT SHELF Completed