Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM00891
Parcel: 11615194B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00891
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00891/2502 6/30/05

1. Provide size of conductors for panel feeders.
2. Load calculation on top of drawing may only be used per NEC 220.30 (A) for feeders of minimum ampacity 100A. Not even indicated per Comment #1 above. In any case, since the load calculations for each feeder were already performed on the panel schedules, this portion is redundant and may be removed.
3. Provide load calculations for ultimate service load.
06/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listing information for the ventless dryer.
07/01/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/05/2005 DROBEY1 WWM REVIEW Needs Review