Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00891
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/30/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00891/2502 6/30/05 1. Provide size of conductors for panel feeders. 2. Load calculation on top of drawing may only be used per NEC 220.30 (A) for feeders of minimum ampacity 100A. Not even indicated per Comment #1 above. In any case, since the load calculations for each feeder were already performed on the panel schedules, this portion is redundant and may be removed. 3. Provide load calculations for ultimate service load. |
| 06/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide listing information for the ventless dryer. |
| 07/01/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/05/2005 | DROBEY1 | WWM | REVIEW | Needs Review |