Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM00891
Parcel: 11615194B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00891
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/03/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
06/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts for the clotheswasher and for the bathtub.
2. Relocate the water heater. Reference Section 509, UPC 1994.
3. Provide a riser diagram for the water piping.
4. Resize the main gas line using Table 12-3, UPC 1994.
5. Clarify the recirculation of the hot water.
06/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
06/29/2005 ROBERT SHERRY WATER REVIEW Approved
06/29/2005 JIM EGAN FIRE REVIEW Completed
06/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Confirm the size of the flue for the water heater.
2. Provide listing information for the ventless
dryer.
06/30/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
06/30/2005 GBONILL1 WWM REVIEW Needs Review