Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00884
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Add Owner's Panel load to SES-2, after the multi-family load for the 3 dwelling units has been calculated. 2. Load calculations for SES-1 and SES-3 total 222A. Existing service entrance conductors have been documented by the Registrant as 3/0 Cu, of ampacity 200A according to NEC Table 310.16. This needs to be resolved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 09/19/2005 | SUE REEVES | REJECT SHELF | Completed |