Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM00884
Parcel: 11615194B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00884
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. It is permissible to use the calculation permitted by NEC 220.32, if each dwelling unit is equipped with electric cooking equipment. No such equipment is indicated on the plans. The Exception allows this Optional Calculation to be used, only if 8 KW is added per unit.
2. Current version of the plans deleted the feeder load calculation, and refers us to the service load calculation. Feeder load calculation is still necessary.
3. Add Owner's Panel load to SES-2, after the multi-family load for the 3 dwelling units has been calculated.
4. Sheet E-1 documents 2/0 Service Entrance Conductors, typical. Ampacity 175A per NEC Table 310.16. Sheet E-2 documents SES-1 and SES-3 as 225A. Coordinate sheets and clarify.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2005 DELMA ROBEY OUT TO CUSTOMER Completed
08/31/2005 SUE REEVES REJECT SHELF Completed