Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00884
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. It is permissible to use the calculation permitted by NEC 220.32, if each dwelling unit is equipped with electric cooking equipment. No such equipment is indicated on the plans. The Exception allows this Optional Calculation to be used, only if 8 KW is added per unit. 2. Current version of the plans deleted the feeder load calculation, and refers us to the service load calculation. Feeder load calculation is still necessary. 3. Add Owner's Panel load to SES-2, after the multi-family load for the 3 dwelling units has been calculated. 4. Sheet E-1 documents 2/0 Service Entrance Conductors, typical. Ampacity 175A per NEC Table 310.16. Sheet E-2 documents SES-1 and SES-3 as 225A. Coordinate sheets and clarify. |