Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00878
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/28/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/28/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 02/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00876 DENIED 2/28/05 1. Put smoke detectors on panel schedules. 2. Verify that the 35 AF at the new AC disconnect was per manufacturer's specifications. If so, document such on the plans. If not, either size the fuses per NEC Article 430 Part III, or add a note to plans requiring the Contractor to size overload protection per manufacturer's requirements. 3. Provide power requirements for ceiling fans, and add to load calculations. 4. Provide location of existing service and existing panels such that Electrical Plans Examiner may evaluate whether fault calculations need to be performed to verify that the relocated panels are rated for their AFC at their new location. |
| 02/28/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 03/01/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |