Permit Number: T05CM00878
Parcel: 126011160

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00878
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2005 JIM EGAN FIRE REVIEW Approved
02/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/28/2005 ANY BUILDING-COMMERCIAL REVIEW Approved
02/28/2005 ROBERT SHERRY WATER REVIEW Approved
02/28/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
02/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00876 DENIED 2/28/05

1. Put smoke detectors on panel schedules.
2. Verify that the 35 AF at the new AC disconnect was per manufacturer's specifications. If so, document such on the plans. If not, either size the fuses per NEC Article 430 Part III, or add a note to plans requiring the Contractor to size overload protection per manufacturer's requirements.
3. Provide power requirements for ceiling fans, and add to load calculations.
4. Provide location of existing service and existing panels such that Electrical Plans Examiner may evaluate whether fault calculations need to be performed to verify that the relocated panels are rated for their AFC at their new location.
02/28/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
03/01/2005 GERRY KOZIOL WWM REVIEW Passed