05/24/2005 SEPTIC APPROVAL WWM REVIEW Denied Septic review submitted on 5/26/05 by Kathy. Review has not been done yet.
06/04/2005 HEATHER THRALL ZONING REVIEW Approved
06/06/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm00842

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Two floor plans are provided. Include plans for desired floor plan only. Remove other plans
2. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2.

4. Sidelights on French doors must be tempered.

Structural Plan

1. PA51 holdown will not work on a stemwall application. Provide holdown that will interface with stemwall. Note type on plans.
2. Cross-section - Dimension 6" from finished grade to bottom of post.



Electrical Plan

1. Provide ground for sub-panel C.
2. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42.

4. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup.
5. Electric for radiant floor heating pumps?

MODEL ENERGY CODE:

1. Provide energy calculations per the 2000 IECC and comply with IRC chapter 11 or 'Rescheck' (DOE) that support chosen 'R' and 'U' values.