The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00840
Parcel: 112073200

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE

Permit Number - T05CM00840
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2005 ANDREW CONNOR NPPO REVIEW Passed
04/04/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner


PROJECT: T05CM00840
2826 E. Alta Vista Street
Single family residence - porch and carport additions
Site plan
1st Review
Transmittal date: April 5, 2005

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please provide the address number on the revised site plan.

2. The minimum type size is 12 point, which needs to be corrected in several areas of the submitted drawings.

3. On the resubmittal, please dimension all elevation views.

4. Please show all utility lines for this location on the revised site plan.

5. The full legal description for the lot must be provided on the resubmitted site plan.

6. Please provide staff with a copy of the last city approved site plan for this property, showing the Board of Adjustment variance approval for the existing carport constructed at the east lot line.

7. The floor and site plans submitted do not match. Please show the proposed additions on the floor plan, labeling all interior/exterior areas on the floor plan and building footprint dimensions.

8. The proposed carport addition at the east side of the property does not meet the current Land Use Code setback requirements. The required setback for the carport is the greater of six (6) feet or two-thirds the height of the exterior building wall. The setback, as proposed on the submitted site plan at two (2) feet, is insufficient and will require seeking such a reduced setback through the Lot Development Option process.

9. These are not final comments for an official Lot Development Option (LDO) referral. Please contact me at Heather.Thrall@tucsonaz.gov or at 791-5608x1156 to make an office appointment to obtain official LDO comments.


If you have any questions about this transmittal, please call (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2005 TAMI ACHONG OUT TO CUSTOMER Completed
04/08/2005 ANGIE SHOFFSTALL REJECT SHELF Completed