Permit Number: T05CM00839
Parcel: 133163020

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T05CM00839
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2005 JIM EGAN FIRE REVIEW Approved
06/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/01/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/01/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved 7/1/05 Need panel schedule.

T05CM00839 7/27/05

1. Per NEC 210.11 (C) (3), the 20-A branch circuit provided to supply the bathroom outlet receptacle shall have no other outlets. Please rearrange branch circuits such that lights are not on the same circuit.

2. Fault calculations use 240V. This is 120/208V according to the line diagram and panel schedule. Please clarify, and verify that the AC and Range, as residential appliances, operate at 208 L-L.