Permit Number: T05CM00833
Parcel: 131090120

Address:
5714 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00833
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water pressure and water pipe sizing calculations per Sections 610.4 and 610.7, UPC 1994.
2. Revise the design water pressure used in the calculations in accordance with Section 610.7 (5), UPC 1994.
02/24/2005 ROBERT SHERRY WATER REVIEW Approved
02/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the facility has adequate ventilation. Reference Section 403.3, IMC 2000.
02/25/2005 DMANN1 FIRE REVIEW Passed
02/25/2005 GERRY KOZIOL WWM REVIEW Approved
02/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Toilet room #2 - turning radius clear of door swing.
2) Toilet room #2 - provide water closet clearance.
3) Provide wall section for interior partition / connections at top and bottom.
4) Occupant load over 15 therefore provide 1 female and 1 male restroom facility. See code section 2902.2.
02/25/2005 CRAIG GROSS ZONING REVIEW Approved
02/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00833 DENIED 2/25/05

Please clarify subfeed to Ckts 13-20. Discuss with Electrical Plans Examiner.
02/25/2005 MATT FLICK ENGINEERING REVIEW Approved No floodplain per FIRM.

Existing civil facilities.

TI only.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
03/01/2005 SUE REEVES REJECT SHELF Completed