Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Photovoltaic source circuits between Row Box and Disconnect, and between Disconnect have not been specified. Suggest THHN, which is rated to higher temperatures, which has been specified on the AC side.
2. Specify that the wiring method between modules, comes with the listed panels.
3. Technical description indicates that wiring box can be separated from sealed inverter enclosure. Please specify that the DC disconnect on the plans is in such separate enclosure.

5. For each disconnecting means which may be energized in the open position, specify a warning sign per NEC 690.17, and specify the exact wording on the plans.
6. Size the conductor bonding the separate AC and DC Grounding Electrodes together.