Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Photovoltaic source circuits between Row Box and Disconnect, and between Disconnect have not been specified. Suggest THHN, which is rated to higher temperatures, which has been specified on the AC side. 2. Specify that the wiring method between modules, comes with the listed panels. 3. Technical description lists an optional external DC-Breaker. Specify if the disconnect on the plans is this optional equipment on the Sunny Boy inverter. 4. Specify the circuit breaker rating on the DC disconnect, on plans. 5. For each disconnecting means which may be energized in the open position, specify a warning sign per NEC 690.17, and specify the exact wording on the plans. 6. Size the conductor bonding the separate AC and DC Grounding Electrodes together. |