Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM00779
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Identify the extent and classification of the Hazardous Location. Electrical Plans Examiner will then evaluate plans for proper specification of methods, materials, any necessary seal-offs, etc. 2. New Service Entrance Section is braced for 30KA AFC, but Meter Main/Circuit Breaker braced for 10KA per Keynote 3. Please clarify, but note that there are 13,900 A AFC from TEP. 3. According to the Fault Calculations, F1 at the Control Panel is 12,670 A. Electric System Specifications 7.11.1 calls for this equipment to be rated at 10K. Please clarify. 4. Minimum font size is 10 pint, which is a little over 1/8". Please enlarge all text as applicable. 5. There is no such NEC Section as 346. See Keynotes 2 (Elevation) and 4 (Plans). Please clarify. Note that the applicable Electrical Code is 2002. Thus the references with "-" should be clarified and corrected to their "." equivalents. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/01/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 03/01/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |