Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/18/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
02/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00738 DENIED 2/18/05 1. The note by the switchboard calls for the breaker feeding the panel to be series tested allowing 14K rated breakers in the panel. A breaker does not directly feed the panel. And the panel is rated for 10K. Clarify intent. 2. It appears that phase A load totals to 15786 VA, not 12,516. This would increase the final service loading to 597A, which, because it is so close to capacity, should be corrected. |
02/18/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/18/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
02/22/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) JUSTIFY ALLOWABLE SQ. FT. CAN BE NONSEPARATED USE. JUSTIFY ALLOWABLE SQ. FT. EQUALS UNLIMITED. 2) EXPIRED PERMITS NEED TO BE CLEARED BEFORE ISSUING NEW PERMIT. |
03/08/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
03/08/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
03/08/2005 | CAGUILA1 | FIRE | REVIEW | Needs Review |