Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/18/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00738 DENIED 2/18/05

1. The note by the switchboard calls for the breaker feeding the panel to be series tested allowing 14K rated breakers in the panel. A breaker does not directly feed the panel. And the panel is rated for 10K. Clarify intent.
2. It appears that phase A load totals to 15786 VA, not 12,516. This would increase the final service loading to 597A, which, because it is so close to capacity, should be corrected.
02/18/2005 ROBERT SHERRY WATER REVIEW Approved
02/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/22/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) JUSTIFY ALLOWABLE SQ. FT. CAN BE NONSEPARATED USE. JUSTIFY ALLOWABLE SQ. FT. EQUALS UNLIMITED.
2) EXPIRED PERMITS NEED TO BE CLEARED BEFORE ISSUING NEW PERMIT.