Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2005 WILDAN BUILDING-RESIDENTIAL REVIEW Approved
04/06/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Rick Thornhill DATE: April 6, 2005
Owner
3352 S. Palo Verde
Tucson, Arizona 85713

SUBJECT: 8753 E. Honey Bear Place
Site plan T05CM00712 (First Review)
Flood Plain Use Permit T05OT00363 (First Review)
T13S, R15E, Section 34

RESUBMITTAL REQUIRED: Site Plan and Flood Plain Use Permit.

The Site Plan (SP) and Flood Plain Use Permit (FUP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15. Available from the Final and Tentative Plat.
3. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
4. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
5. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22.
6. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
7. Show Site plan number on all sheets per D.S. 2-02.2.1.29.
8. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01.
9. Minimum Finished Floor Elevation shall be 2534.0.
10. An Elevation Certificate, prepared by a registered land surveyor, will be required prior to the issuance of the Certificate of Occupancy.

Flood Plain Use Permit:
1. Show the 100-year flood plain limits per the final plat.
2. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
3. Minimum Finished Floor Elevation shall be 2534.0.
4. An Elevation Certificate, prepared by a registered land surveyor, will be required prior to the issuance of the Certificate of Occupancy.


If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8753 E. Honey Bear Place site
04/07/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2005 KMEDINA1 OUT TO CUSTOMER Completed