Permit Number: T05CM00692
Parcel: 10609062C

Review Status: Completed

Review Details: REVISION

Permit Number - T05CM00692
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00692 7/27/05

1. Per Electrical Lighting Plan, sign and lights are on Citcuits 4 and 6. Such Ckts have receptacles only on Panel Schedule.

2. MOCP for AC is 45 AF per Equipment Schedule Sheet M2. No such fuse on plans.
07/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the installation of the floor sink.
07/29/2005 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/29/2005 SUE REEVES OUT TO CUSTOMER Completed