Permit Number: T05CM00692
Parcel: 10609062C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00692
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
02/16/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
02/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide all of the loads and developed lengths of the natural gas piping served by the gas meter. Show a gas riser diagram.
02/17/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ADJACENT OCCUPANCIES FOR SEPERATED USE AND RATING OF DEMISING WALLS.
2) ACCESSIBILTY FOR RESTROOM PER ANSI STANDARDS A117.1 OR JUSTIFY 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS MEETING THE STANDARDS.
02/17/2005 ROBERT SHERRY WATER REVIEW Approved
02/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise detail A/M1 to comply with Section 507.3.5, UPC 1994.
03/16/2005 JIM EGAN FIRE REVIEW Approved
03/16/2005 DROBEY1 WWM REVIEW Needs Review