02/16/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing fixtures required by Chapter 29, IBC 2003 for Storage occupancy.
2. Revise the water pipe sizing per Section 610.4, UPC 1994.
02/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00688 DENIED 2/18/05

1. Show new Water Heaters on plans. Disconnects and panel and circuit numbers.
2. This occupancy is S-1, or Storage. Exceeds 2000 IECC Lighting Power Budget of 1.0 W/SF. By the number of receptacles it appears that something else is going on here. Willing to discuss.
3. Keynote 6 has 200A disconnect to Panel CH, which is on a 100A sub-feed from Panel CHM. Clarify.
4. There are two Keynotes 11. Clarify.
02/17/2005 ROBERT SHERRY WATER REVIEW Approved
02/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the duct insulation complies with Section 803.2.8, IECC 2000.
02/24/2005 TACHONG1 ZONING REVIEW Needs Review
02/24/2005 TACHONG1 WWM REVIEW Needs Review
02/24/2005 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
02/24/2005 TACHONG1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2005 TAMI ACHONG OUT TO CUSTOMER Completed