Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00688
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
02/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing fixtures required by Chapter 29, IBC 2003 for Storage occupancy. 2. Revise the water pipe sizing per Section 610.4, UPC 1994. |
02/17/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00688 DENIED 2/18/05 1. Show new Water Heaters on plans. Disconnects and panel and circuit numbers. 2. This occupancy is S-1, or Storage. Exceeds 2000 IECC Lighting Power Budget of 1.0 W/SF. By the number of receptacles it appears that something else is going on here. Willing to discuss. 3. Keynote 6 has 200A disconnect to Panel CH, which is on a 100A sub-feed from Panel CHM. Clarify. 4. There are two Keynotes 11. Clarify. |
02/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the duct insulation complies with Section 803.2.8, IECC 2000. |
02/24/2005 | TACHONG1 | ZONING | REVIEW | Needs Review | |
02/24/2005 | TACHONG1 | WWM | REVIEW | Needs Review | |
02/24/2005 | TACHONG1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
02/24/2005 | TACHONG1 | FIRE | REVIEW | Needs Review |