| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/28/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/17/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 3/22/05 ACTIVITY NUMBER: T05CM00658 PROJECT NAME: Replace Inlet piping & upgrade elect. PROJECT ADDRESS: 1255 S. Beverly Ave. ARCHITECT / ENGINEER: Dorothy Dolan PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Clarify chemicals if any stored on site. 2) Detail riser heights for stairs see section 1009.3 & 1009.3.2 3) Hand rails @ stairways per section 1009.11 - height, extensions, & graspability. 4) Grating support detail 1, and section 2 - sheet 18 of 35. Details require ¼" x 7" x cont. strap. Structural calculations specifies ¼" x 8" x cont. strap. 5) Special Inspection Forms will need to be provided before permit can be issued. |