Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00656
Parcel: 136061570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00656
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2005 JIM EGAN FIRE REVIEW Approved
02/15/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
02/15/2005 DAN CASTRO ZONING REVIEW Approved
02/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t05cm00656 DENIED 2/15/05
1. Fill in load on panel schedule for Ckts D-39 and D-41.
2. Add 25% for continuous load for RTU #1 to Panel D load calculation, and to service load calculation.
3. City of Tucson does not allow the use of the "Up-Over-Down" method to attenuate fault current. Either fully rate Panel D, or specify its "downstream" AFC rating such the the note calling for series rating covers any and all requirements to deal with the AFC at the new Panel.
4. In the service load calculations, please revisit the counting of 250 VA for 88 lighting fixtures. This appears to be a high amount for a fixture type which was in such number at a location such as this.
5. Correct Keynote #2 on Sheet E-1, such that only the panel intended for relocation is indeed relocated.
02/15/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
02/16/2005 TACHONG1 PLUMBING-COMMERCIAL REVIEW Needs Review
02/16/2005 GERRY KOZIOL WWM REVIEW Approved
02/16/2005 TACHONG1 MECHANICAL-COMMERCIAL REVIEW Needs Review
02/16/2005 TACHONG1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2005 TAMI ACHONG OUT TO CUSTOMER Completed