Permit Number: T05CM00655
Parcel: 136061570

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00655
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00656 DENIED 2/16/05

Previous Review Comment #3 called for the specification of the lower-rated overcurrent device in the series rating. Please note that per NEC 240.86 (B), series ratings shall not be used where the motors are connected on the load side of the higher-rated OC device and the Line side of the lower-rated OC device if the sum of the motor FLA exceeds 1% of the lower OCPD rating.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2005 TAMI ACHONG OUT TO CUSTOMER Completed