Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Site plan, floor plan, and finish floor plan text sixe must be a min. of 10 pt. Please correct.
2) provide code analysis justifying use - seperated/non-seperated use?
3) Show water closet envelope for floor clearance.
02/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00625 DENIED 2/14/05
1. Provide cut sheets for fixtures C and F. Need to show power requirements.
2. On Lighting Plan, provide panel and circuit number for lighting fixtures on circuit with (7) (C), (4) (F), and (4) (E). Could be counter lights, A-3.
2000 IECC lists allowable power for lights in banking 2.0 W/SF. Please revisit calculations.
02/14/2005 ROBERT SHERRY WATER REVIEW Approved
02/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/22/2005 DROBEY1 FIRE REVIEW Needs Review
02/22/2005 DROBEY1 WWM REVIEW Needs Review
02/22/2005 DROBEY1 ZONING REVIEW Needs Review
02/22/2005 DROBEY1 ENGINEERING REVIEW Needs Review