Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00625
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Site plan, floor plan, and finish floor plan text sixe must be a min. of 10 pt. Please correct. 2) provide code analysis justifying use - seperated/non-seperated use? 3) Show water closet envelope for floor clearance. |
| 02/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00625 DENIED 2/14/05 1. Provide cut sheets for fixtures C and F. Need to show power requirements. 2. On Lighting Plan, provide panel and circuit number for lighting fixtures on circuit with (7) (C), (4) (F), and (4) (E). Could be counter lights, A-3. 2000 IECC lists allowable power for lights in banking 2.0 W/SF. Please revisit calculations. |
| 02/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 02/22/2005 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 02/22/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 02/22/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 02/22/2005 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |