Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00610
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 02/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | 1) CLARIFY RESTROOM FACILITIES THAT MEET ANSI A117.1 STANDARDS. 2) CLARIFY EXIT SIGN FOR COMBINED SUITE. 3) CLARIFY EXIT PATH MEETS ANSI STANDARD A117.1. |
| 02/11/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/06/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/06/2005 | CHRISTY FOREMAN | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/06/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/06/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/06/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the project areas are being provided with adequate ventilation. Reference Section 403.3, IMC 2000. 2. Mechanical specification item #14 calls for the air flow to be balanced as shown on the drawing; show the balancing data. |
| 04/19/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |