Permit Number: T05CM00604
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00604
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
02/17/2005 JIM EGAN FIRE REVIEW Approved
02/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00604 DENIED 2/17/05

1. Add 25% for continuous load on Panel SWGR. This would include any continuous loading on the two panels powered from SWGR. Or please justify otherwise. This comment was made on the first review.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2005 BETH GRANT OUT TO CUSTOMER Completed