Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM00604
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE SITE PLAN WITH PROPERTY LINES AND COSE ANALYSIS. |
02/11/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
02/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00604 DENIED 2/11/05 1. Add 25% for continuous load on Panel SWGR. This would include any continuous loading on the two panels powered from SWGR. 2. There is no load on Panel SWGR for the Ball Field Lighting Cabinet, but there is a 150/3 circuit indicated for this load. Please clarify. |
02/11/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
02/16/2005 | LLESNY1 | FIRE | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/16/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |