Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00604
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00604
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE SITE PLAN WITH PROPERTY LINES AND COSE ANALYSIS.
02/11/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00604 DENIED 2/11/05
1. Add 25% for continuous load on Panel SWGR. This would include any continuous loading on the two panels powered from SWGR.
2. There is no load on Panel SWGR for the Ball Field Lighting Cabinet, but there is a 150/3 circuit indicated for this load. Please clarify.
02/11/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
02/16/2005 LLESNY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2005 LISA LESNY OUT TO CUSTOMER Completed