Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T05CM00598
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/18/2005 | MICHAEL ST. PAUL | ZONING HC SITE | REVIEW | Passed | |
| 03/18/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 03/29/2005 | ANDREW CONNOR | NPPO | REVIEW | Denied | Include the correct address on Application for Exception. |
| 04/08/2005 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a Revise note on landscape to include proper code section LUC 3.7.2.3.A.1.a. 2. Add note to indicate: Replacement in case of damage or death of existing trees to meet COT requirements. 3. Indicated on grading plan (Sheet 6 of 7) within eastern portion of basin Keynote 8 is used incorrectly revise plan as necessary. 4. Provide a 30" screen along the entire frontage of Grant Rd. on landscape and grading plan per LUC 3.7.2-I 5. Submit NPPO plan or Application for Exception per DS 2-15.0 Include the correct address on Application for Exception. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |
| 04/11/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |