Permit Number: T05CM00576
Parcel: 11720016G

Address:
110 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00576
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Passed
02/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the termination of the roof drain that is accepting the blowdown from the cooling towers complies with Section 307.2.1, IMC 2000.
02/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/11/2005 ROBERT SHERRY WATER REVIEW Approved
02/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide a reduced pressure backflow assembly for the water make-up to the cooling towers.
02/22/2005 CAGUILA1 FIRE REVIEW Needs Review