Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00576
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/11/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Passed | |
02/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the termination of the roof drain that is accepting the blowdown from the cooling towers complies with Section 307.2.1, IMC 2000. |
02/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a reduced pressure backflow assembly for the water make-up to the cooling towers. |
02/22/2005 | CAGUILA1 | FIRE | REVIEW | Needs Review |