Permit Number: T05CM00575
Parcel: 110121000

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00575
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2005 JIM EGAN FIRE REVIEW Approved
02/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/10/2005 KMARION1 BUILDING-COMMERCIAL REVIEW Approved
02/10/2005 ROBERT SHERRY WATER REVIEW Approved
02/10/2005 DAN CASTRO ZONING REVIEW Approved
02/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00575 DENIED 2/10/05
1. It appears that DB-14 is used twice, since it powers microwave in break room and also receptacles in MD area, on different circuits.
2. Please put the following note in a prominent place on the plans: "All work in patient care areas shall comply with NEC 517.13."
3. Please change the reference to the 1998 IECC to read "2000."
4. Since the service entrance conductors (3) (500) = 1500 MCM, the Grounding Electrode conductor, sized per NEC Table 250.66, shall be 3/0, not 2/0. The Main Bonding Jumper shall be 4/0. Reference NEC 250.102 (C) and Table 8.
(3) (500) (0.125) = 187.5.
5. Note on Single Line Diagram refers to "Grounding Detail A" on Sheet E1.1. No such detail.
6. The 2/0 GND between the TEP X'FMR and the Term. Box is redundant, and shall be deleted.
02/10/2005 DOUG WILLIAMS ENGINEERING REVIEW Approved
02/17/2005 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2005 TAMI ACHONG OUT TO CUSTOMER Completed