Permit Number: T05CM00545
Parcel: 12620001C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00545
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2005 JIM EGAN FIRE REVIEW Approved
02/09/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/09/2005 ANY BUILDING-COMMERCIAL REVIEW Denied S1. Provide site plan showing relationship of this building by dimension to adjacent buildings.
S2. Show fire ratings of walls.
S3. Address damper rquirements.
02/09/2005 ROBERT SHERRY WATER REVIEW Approved
02/09/2005 MICHAEL ST. PAUL ZONING REVIEW Passed
02/09/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide fire damper at duct penetration in storage room.
02/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00545 DENIED 2/9/05

1. Per the values of the AC Unit Schedule on Sheet M-3, a total of the 3 compressors, indoor air, and outdoor air would be 273 A. Total for service exceeds 800 A. Please re-evaluate load calculations and/or loads on this service.
02/09/2005 LOREN MAKUS ENGINEERING REVIEW Approved
02/11/2005 GERRY KOZIOL WWM REVIEW Passed