Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00545
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/09/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
02/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
02/09/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | S1. Provide site plan showing relationship of this building by dimension to adjacent buildings. S2. Show fire ratings of walls. S3. Address damper rquirements. |
02/09/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/09/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
02/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide fire damper at duct penetration in storage room. |
02/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00545 DENIED 2/9/05 1. Per the values of the AC Unit Schedule on Sheet M-3, a total of the 3 compressors, indoor air, and outdoor air would be 273 A. Total for service exceeds 800 A. Please re-evaluate load calculations and/or loads on this service. |
02/09/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
02/11/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/11/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |