Permit Number: T05CM00542
Parcel: 114491110

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM00542
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2005 GERRY KOZIOL WWM REVIEW Denied needs to build public sewer
02/28/2005 PAUL MACHADO ENGINEERING REVIEW Approved
03/10/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Approved PLAN CHECK COMMENTS - PROJECT #T05CM00542

3/11/05 2474 N. WRENS NEST PL.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. PLEASE MOVE THE DIMENSION FOR THE PLUMBING WALL ADJACENT SONIA'S ROOM OFF THE FOOTING LINE, FOR CLARITY, AND CHECK THE DIMENSION FOR ACCURACY.

STRUCTURAL PLANS:

1. 14' TJI SERIES 110 @ 16" APPEAR TO BE OVER SPANNED OVER THE GARAGE. PLEASE CHECK WITH TRUSS JOIST-MACMILLAN. THE TABLE THEY GAVE US APPROVES THEM FOR 25'-1".

2. SPECIFY THE HEADER FOR THE DOORWAY TO CONOR'S ROOM.

3. SPECIFY THE HEADER FOR THE ARCHWAY BETWEEN THE DEN/STUDY AND THE GREAT ROOM.

4. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

SECTIONS - DETAILS - MISC. NOTES:

1. 1, 2 / 2 ; PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLTS. R403.1.6 .

2. PROVIDE 1-#4 CONTINUOUS IN THE "STEMWALL". R403.1.3.1 .

3. KEYNOTE 4 / 4 ; PROVIDE 2 LAYERS OF UNDERLATMENT FOR THE TILE ROOF SLOPED AT 4 : 12 . R905.3.3.1 .

4. 3, 9 / 5 ; PLEASE SPECIFY "SAG-RESISTANT" ½" GYP. BD. ON CEILINGS FRAMED AT 24" O.C. TABLE 702.3.5 FOOTNOTE D .

5. 3 / 5 ; DETAIL CALL FOR A TAPERED PARAPET AND REFERS TO DETAIL 1 FOR PARAPET DETAIL. DETAIL 1 SHOWS POP-OUTS vs TAPER. NOT A CODE ISSUE.

6. 6 / 5 ; PROVIDE RAFTER / BEAM CONNECTION.

7. DTLS. / 5 ; PLEASE SHOW THE INSULATION AT THE TOP CHORD OF THE TRUSSES.

PLUMBING PLANS:

1. PLEASE SPECIFY THE WATER METER SIZE.

2. PROVIDE GAS TO FURNACE #2. THIS GAS LINE MAY BE MISPLACED IN THE GARAGE.

MECHANICAL:

1. THE SUPPLY AND RETURN AIR TRUNKS APPEAR TO BE UNDER SIZED. M1403.1 .

2. PLEASE SIZE THE COMBUSTION AIR FOR THE GAS APPLIANCES IN THE GARAGE. TABLE 5-A, UPC STATE AMENDMENTS.


ELECTRICAL PLANS:

1. THE FURNACE RECEPTACLE IN THE GARAGE SHOULDN'TBE ON THE BATH ROOM RECEPTACLE CIRCUIT.



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/23/2005 SUE REEVES REJECT SHELF Completed